+141osamarady dyaa eldeen jeopenny20 Zaoui Hamid aminegica Mohamed Abashr م علي شريدة haddad Adnan حسني إمام mostafa173 sherief faycaal houssam_algerie Olimat.Qais meziani mohamedtawab سعّودي azouzi mimo rafidrz hassan77.mohamed77 michael التقني المتخصص radouan AHMED200100 الحابى وبس AYMAN ALY mk_asmar assem fahed alnefawi ibrahimabugabal جميل33 matil redouane oelhoseny م. أحمد الصوي amico azzouz shreif rajwa amerelect يائل ghas khadija_maroc abou hafs hathout محمد حنيجل amera jubara شريف المغني كريستآل zakaria echatri abddabbour 0-1 اشرف حلايقه hamdahmad marso mohamed_moussaoui DOER Ali Abdulraoof rachid emsi محمد صبحى زكى المشرقى tariksteel محسن علي حسين mjalil80 wajdi ahmed saad eng_mo7amed_3ly mikah elec مهندس محمد رفعت نوروملك عادل jad raddad yahiaadam mahmouddwedar amro moh mohammad-aw mohamed fathy eldeery khalid abualrub mgdy doaa mobasher ahmedhasan alaaproject محمود فرغل hatemnoby احمد سيد RAED amermesbahi abdo laola harith esem2704 ahmedkasmi عطية السيد مرسى hamadaaskar mahmoud01614 sharkfish77 asdsaad نجم السعد merou1965 eng_hosny محمد منصور أحمد رأفت Karim Elsayed رزاق amr_fee ابو يوسف الفقير لله صابر يوسف ريان نشوان eng_mah66 mostafasadek79 هاني التميمي sea مهندس_السيد ams_tee احمدسامى مهندس علي مهندس خالد_بنداري حسام السيد ذكى abd elkader ميدو ATHEER yassseeen lotfy esaed rafaa azizi محمد ابراهي ahmad yousef neoala بلال درويش ابراهيم بهجت على msaa60 Alewan abo gamel AHMAD ZOOY شرشابيل obada ensan me محمد الزوكاني m_elshatr محمود فيصل صبره mm man3660 RAMA metwally.mustafa PLCMan 145 مشترك |
|
كاتب الموضوع | رسالة |
---|
msaa60 عريف
عدد الرسائل : 12 العمر : 41 تاريخ التسجيل : 31/03/2010
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الأحد 4 أبريل 2010 - 4:50 | |
| [img] By msaa600 at 2010-04-04[/img] | |
|
| |
metwally.mustafa فريق أول
عدد الرسائل : 4226 العمر : 38 الموقع : Egypt العمل/الترفيه : automation engineer تاريخ التسجيل : 12/01/2009
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الأحد 4 أبريل 2010 - 6:01 | |
| لاحظ اخى الكريم من تسميه موديول الدخل والخرج حيث انك سميتهIB2
وهو المفروض ان يكون IB0
كذلك موديول الخرق فقد سميتهQB1
وهو المفروض ان يكونQB4 حسب تسميته فى البرنامج
لاحظ انه لابد من ان يكون هناك توافق بين الرموز المستخدمه فى برنامج المحاكاه
والرموز المستخدمه فى كتابه البرنامج نفسه
اتمنى لك التوفيق _________________ I am so far behind, I think i am first
| |
|
| |
msaa60 عريف
عدد الرسائل : 12 العمر : 41 تاريخ التسجيل : 31/03/2010
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الأحد 4 أبريل 2010 - 8:15 | |
| | |
|
| |
ابراهيم بهجت على مساعد أول
عدد الرسائل : 67 تاريخ التسجيل : 11/04/2009
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الأحد 4 أبريل 2010 - 11:48 | |
| البرنامج المطلوب فى التحكم فى درجه الحراره مع عمل scalling وكذلك اعطاء خرج تماثلى يعبر عن التغير فى درجه الحراره كالاتى الاخ العزيز متولى هل من الممكن اخى العزير كتابتها لى ببرمجة STL واشكرك على سعة صدرك | |
|
| |
metwally.mustafa فريق أول
عدد الرسائل : 4226 العمر : 38 الموقع : Egypt العمل/الترفيه : automation engineer تاريخ التسجيل : 12/01/2009
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الإثنين 5 أبريل 2010 - 3:10 | |
| _________________ I am so far behind, I think i am first
| |
|
| |
metwally.mustafa فريق أول
عدد الرسائل : 4226 العمر : 38 الموقع : Egypt العمل/الترفيه : automation engineer تاريخ التسجيل : 12/01/2009
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الإثنين 5 أبريل 2010 - 4:36 | |
| | |
|
| |
metwally.mustafa فريق أول
عدد الرسائل : 4226 العمر : 38 الموقع : Egypt العمل/الترفيه : automation engineer تاريخ التسجيل : 12/01/2009
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الإثنين 5 أبريل 2010 - 4:47 | |
| لاحظ اخى الكريم ان القيمه الصحيحه للاشاره بعد تخزينها على MD10 هى
MW12 وليس كل الرقم المتغير حيث ان MD10=MW10+MW12
واليك هذا الشرح الذى قدمه المهندس حسن فى احد التطبيقات المهمه
"أما بخصوص موضوع التحويل من Double integer إلى Integer أو التحويل من رقم صحيح ذو دقة مضاعفة 32 خانة إلى رقم صحيح 16 خانة فإن الأمر يقوم أساسا على طريقة التخزين
بمعنى : نفترض مثلا أنه لدينا الرقم 1500 وهو رقم صحيح بالنظام العشري
وعند تمثيله بالنظام الثنائي فإن هذا الرقم يصبح 00000000000000000000010111011100
وهذا الرقم أخي العزيز يتم تخزينه إذا كان Double integer في عدد 2 word أو 32 خانة كما ذكرنا ويتم التخزين في ثلاث مناطق :
الخانة السوداء وهي تمثل الإشارة فإن كان بها 1 يكون الرقم سالب وإن كان صفرا مثل حالتنا يكون الرقم موجب والجزء الأحمر والأخضر هما قيمة الرقم ولكن عند عمل العنونة Addressing فإن التخزين كما قلنا يتم في عدد 2 word ويتم تخزين الجزء الأحمر في Higher word وتخزين الجزء الأخضر والاسود في Lower word وبالتالي لو مثلا تم التخزين على MD100 فإنها تشمل MW100, MW102 وعليه يكون الجزء الأحمر في MW102 والجزء الأخضر والأسود في MW100
فإذا أردنا الحصول على قيمة الرقم نأخذ MW102 وهذا ما أشرنا إليه سابقا
ولكن المشكلة الرئيسية هي عندما يكون الرقم سالب فإنه عند الحصول فقط على قيمة الرقم سوف يصبح الرقم موجب وهذا مخالف للواقع لهذا فيجب بعد أخذ القيمة التحويل بالضرب في -1 للحصول على القيمة السالبة" _________________ I am so far behind, I think i am first
| |
|
| |
ابراهيم بهجت على مساعد أول
عدد الرسائل : 67 تاريخ التسجيل : 11/04/2009
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الإثنين 5 أبريل 2010 - 17:58 | |
| ادام الله لك فى بصيرتك العلمية لقد استوعبت هذا الدرس منك جيدا واشكر على معلوماتك التى لاتبخل بها على احد وارجوا الاتنسى الطلب الثانى وهو كيف يتم التعامل بنظام F.I F.O واريد امثلة على استخدامها FIRST OUT POUT FIRST IN POUT وان كان يوجد ملف لشرحة فارجوا المساعدة وشكرا | |
|
| |
abo gamel رائد
عدد الرسائل : 288 العمر : 45 الموقع : سورية حلب العمل/الترفيه : مهندس الكترون تاريخ التسجيل : 03/08/2009
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الجمعة 9 أبريل 2010 - 5:04 | |
| اشكرك استاذ حسن قمت بازالة الmmc من المتحكم وقمت بفورمات لها وتخلصت من ال passwordعليها وتم المطلوب بفضل الله وبمساعدتك .................. عزرا لكترة الاسئلة ايضا لدينا s7 414 -3dp وs7 300و------تعمل بدون mmc -------وايضا محمية ب password وايضا لدينا برنامج التطبيقي الاساسي والمطلوب فورمات للمتحكم لازالة ال password ومع الملاحظ ان الخيار DIIAGNOSTIC /SETTING CLEAR /RESET غير مقعل الا بعد ONLINE مع المتحكم اي لا استطيع مسح محتويات المعالج الا بعد الاتصال معه(ONLINE MODE) وهناك PASSWORD يجب ازالته شكرا لك على كل شئ | |
|
| |
بلال درويش عريف
عدد الرسائل : 11 العمر : 39 تاريخ التسجيل : 03/02/2010
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الثلاثاء 20 أبريل 2010 - 13:33 | |
| احتاج لشراء شاشه op7 DP و لا اعرف من اين يمكنني شراءها داخل مصر | |
|
| |
PLCMan Admin
عدد الرسائل : 12366 العمر : 55 العمل/الترفيه : Maintenance manager تاريخ التسجيل : 02/03/2008
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الخميس 22 أبريل 2010 - 14:44 | |
| السؤال :
Hi how to delete eeprom memory in 313dp cpu specialy saftey progam blocks
وكانت الإجابة :
How do you reset a SIMATIC S7-300 CPU and MMC (default reset or overall reset)?
Description With S7-300 CPUs, the communication data of the local interface (protocol, baud rate and station address) is retained if no MMC or an MMC with invalid data* is slotted at startup. The CPU can still be reached via the previous communication data. The communication data is changed only in the case of a default reset or when starting up with an MMC with valid data*.
S7 300 CPU With S7-300 CPUs (except CPU 318), the function "Reset in the as-delivered status" is implemented as of firmware version V2.5. In section 9.5 of the operating instructions "S7-300 CPU 31xC and CPU 31x: Setting up" (Entry ID: 13008499) you will find all the information on the effect of and procedure for "Resetting in the as-delivered status".
MMC It is only possible to reset the MMC if it contains data* that is invalid for the CPU. Otherwise the MMC is only initialized by the procedure described.
All the user data is deleted when you reset the SIMATIC Micro Memory Card (MMC). Proceed as follows. The MMC is slotted in the bay of the CPU. The CPU requests an overall reset (slow blinking of the STOP LED). Set the switch to "MRES" and hold it there until the STOP LED lights continuously (approx. 9 seconds). Within the next 3 seconds, you must let the switch go and set it again to "MRES". The STOP LED now blinks during the delete procedure.
If the CPU continues to request an overall reset after the procedure described above, then the MMC is defective.
_________________ أبـوروان | |
|
| |
PLCMan Admin
عدد الرسائل : 12366 العمر : 55 العمل/الترفيه : Maintenance manager تاريخ التسجيل : 02/03/2008
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الخميس 22 أبريل 2010 - 14:47 | |
|
السؤال :
Which devices can you use to read from, write to or delete from an S7-300 MMC (Micro Memory Card) outside the CPU?
وكانت الإجابة :
Device note The SIMATIC Micro Memory Cards (MMCs) of the S7-300 may be read or written only by the following devices outside the CPU: SIMATIC Field PG SIMATIC Power PG USB prommer (order number 6ES7792-0AA00-0XA0).
Using these devices, you can open an MMC in the SIMATIC Manager for reading or writing or for deleting the content. Fig. 01 Note Do not use the MMC for non-SIMATIC purposes and do not format it with a third-party device. This would possibly overwrite the internal structure of the MMC that cannot be restored. In this case, the MMC is no longer recognized/accepted in a SIMATIC S7-300 CPU and can no longer be used with SIMATIC devices.
_________________ أبـوروان | |
|
| |
PLCMan Admin
عدد الرسائل : 12366 العمر : 55 العمل/الترفيه : Maintenance manager تاريخ التسجيل : 02/03/2008
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الخميس 22 أبريل 2010 - 14:56 | |
|
السؤال :
What are the requirements for an online connection between WinCC and an S7 with MPI (CP5611)?
وكانت الإجابة :
S7DOS must be installed. S7DOS is installed automatically in WinCC version V5.0 + SP2 and higher.
If necessary, you can install it from the WinCC CD. Start WinCC Setup and in the "Select Components" dialog you choose "Communication > S7DOS"
The access point defined in the PG/PC interface must match the logical device name of the MPI channel. For example, to use the "S7ONLINE" access point, you must set the PG/PC interface on your MPI communications processor. In the Control Panel you open the "Set PG/PC Interface" program. Select "S7ONLINE" as Access Point and then select your MPI communications processor. If it is not shown in the window, you can install it using the "Select..." button.
A communication channel must exist. Open your WinCC project and add your channel to the Tag Management. To do this, right-click to open the "Add new driver" dialog box and install the "SIMATIC S7 Protocol Suite.CHN" WinCC communications driver.
The access point must be correct. Set the logical device name of the MPI channel to the "S7ONLINE" access point that you selected under (2). In Tag Management you double-click on the communications driver "SIMATIC S7 PROTOCOL SUITE". Right-click on the "MPI" channel and click on the menu command "System Parameter". Click on the "Unit" tab and select the item "S7ONLINE" item in the drop-down list for "Logical device name".
You must create a connection. Then right-click to add a new connection to your S7 or S7 program and give it a name. Example: "S7Programm_AS1".
The connection properties must be correct. In the dialog that opens (in point 5) you click on the "Properties" button and set the connection parameters there. In this case, the CPU has the MPI address "30" and the MPI segment has the ID "0". The CPU is slotted in rack number 0, slot 3.
مع خالص التمنيات بالتوفيق
_________________ أبـوروان | |
|
| |
metwally.mustafa فريق أول
عدد الرسائل : 4226 العمر : 38 الموقع : Egypt العمل/الترفيه : automation engineer تاريخ التسجيل : 12/01/2009
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الجمعة 23 أبريل 2010 - 11:15 | |
| جزاكم الله خيرا اخى الكريم _________________ I am so far behind, I think i am first
| |
|
| |
neoala مساعد أول
عدد الرسائل : 50 العمر : 40 تاريخ التسجيل : 26/04/2010
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الإثنين 26 أبريل 2010 - 11:23 | |
| السلام عليكم ارجوا ان تساعدوني ان اعمل في مصنع واريد عمل نسخة أحتياطية لبرنامج الموجود في plc s300 عن طريق simatic manager مع العلم انا برنامج محمي بكلمة سر وانا أملك كلمة السر ارجوا منكم ان تدلوني على الطريقة. بالصور إذا استطعتم وهل فيها خطورة على البرنامج بحيث اذا ضاع البرنامج يتكبد المصنع خسائر كبيرة مع خالص التمنيات بالتوفيق | |
|
| |
metwally.mustafa فريق أول
عدد الرسائل : 4226 العمر : 38 الموقع : Egypt العمل/الترفيه : automation engineer تاريخ التسجيل : 12/01/2009
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الثلاثاء 27 أبريل 2010 - 12:03 | |
| | |
|
| |
neoala مساعد أول
عدد الرسائل : 50 العمر : 40 تاريخ التسجيل : 26/04/2010
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الثلاثاء 27 أبريل 2010 - 15:07 | |
| | |
|
| |
neoala مساعد أول
عدد الرسائل : 50 العمر : 40 تاريخ التسجيل : 26/04/2010
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الثلاثاء 27 أبريل 2010 - 15:08 | |
| | |
|
| |
ahmad yousef ملازم أول
عدد الرسائل : 104 العمر : 43 الموقع : سوريا-دمشق العمل/الترفيه : مدير صيانة - شركة خاصة تاريخ التسجيل : 07/02/2010
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الأحد 2 مايو 2010 - 1:11 | |
| السلام عليكم جزاكم الله خيرا على هذه الخدمات وجعلها الله في ميزان حسناتكم ادريد ان استفسر انا عندي cpu من شركة سيمنس موديل (simatic 505-555) وانا لا اعلم اي معلومات عنه ولا املك السوفت وير الخاص بة ولا مخطط الكيبل لللاتصال به فهل من الممكن تزويدي بهذا السوفت وير اذا كان ممكنا وإذا وجد pdf شرح عنه . ولكم جزيل الشكر | |
|
| |
PLCMan Admin
عدد الرسائل : 12366 العمر : 55 العمل/الترفيه : Maintenance manager تاريخ التسجيل : 02/03/2008
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الأحد 2 مايو 2010 - 5:32 | |
| - ahmad yousef كتب:
- السلام عليكم
جزاكم الله خيرا على هذه الخدمات وجعلها الله في ميزان حسناتكم ادريد ان استفسر انا عندي cpu من شركة سيمنس موديل (simatic 505-555) وانا لا اعلم اي معلومات عنه ولا املك السوفت وير الخاص بة ولا مخطط الكيبل لللاتصال به فهل من الممكن تزويدي بهذا السوفت وير اذا كان ممكنا وإذا وجد pdf شرح عنه . ولكم جزيل الشكر الأخ العزيز
أولا هذا ملف لشرح البرمجة لهذا النوع من الحاكمات على الرابط التالي
http://support.automation.siemens.com/WW/view/en/10966404
وهذا الإصدار يشمل الوصف الفني لمكونات النظام System manual
http://support.automation.siemens.com/WW/view/en/10966403
وهذا الإصدار خاص ببرنامج البرمجة الخاص بهذا النوع واسمه SIMATIC 505 SoftShop for Windows Rel. 3.0
http://support.automation.siemens.com/WW/view/en/10953134
وهذا الإصدار خاص للبرمجة باستخدام SIMATIC 505 TISOFT2 Release 6.3
http://support.automation.siemens.com/WW/view/en/10953133
وجاري البحث للحصول على برامج التشغيل لهذا النوع من سيمنس
مع خالص التمنيات بالتوفيق
_________________ أبـوروان | |
|
| |
Alewan جندي
عدد الرسائل : 9 العمر : 58 تاريخ التسجيل : 14/03/2010
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الأربعاء 26 مايو 2010 - 8:46 | |
| الاخ / الفاضل المهندس حسن انا أستخدم S7 5.3 SP1 على نظام WINDOWS 2000 PROF و CPU موديل 318 مطلوب كيفية أجرا اتصال مابين PC و PLC نرجو توضيح الخطوات وكدلك كيف يتم أخد نسخة من PROJECT الموجود في CPU نشكر لكم الجهود المبدولة في سبيل ايصال المعلومة لكل الناس وتمنياتي بالتوفيق للجميع | |
|
| |
PLCMan Admin
عدد الرسائل : 12366 العمر : 55 العمل/الترفيه : Maintenance manager تاريخ التسجيل : 02/03/2008
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الأربعاء 26 مايو 2010 - 10:15 | |
| - Alewan كتب:
- الاخ / الفاضل المهندس حسن
انا أستخدم S7 5.3 SP1 على نظام WINDOWS 2000 PROF و CPU موديل 318 مطلوب كيفية أجرا اتصال مابين PC و PLC نرجو توضيح الخطوات وكدلك كيف يتم أخد نسخة من PROJECT الموجود في CPU نشكر لكم الجهود المبدولة في سبيل ايصال المعلومة لكل الناس وتمنياتي بالتوفيق للجميع الأخ العزيز
لديك الآن ثلاثة من متطلبات الاتصال مع PLC S7-300 وهي كما ذكرت : 1- جهاز حاسب PC 2- برنامج Simatic manager S7 V5.3 SP1 مثبت على جهازك 3- وحدة CPU S7-318 ومازال مطلوب أشياء أخرى حتى يتم الاتصال أولها وسيلة الاتصال والتي يمكن أن تكون واحد من الأربعة التالية 1- كارت CP5611 مثلا والذي يتم تثبيته على PCI-Slot in PC مثل الصورة التالية 2- كابل توصيل PC-Adaptor-USB or RS232 حسب منفذ الاتصال لديك وأفضل USB مثل الصورة التالية 3- كابل اتصال من منفذ PCMCIA وهو CP5512 مثل الشكل التالي : 4- كابل إيثرنت مع وحدات CPU التي تدعم منفذ إيثرنت مثل الشكل التالي : والخطوة التالية هو ضبط الاتصال بين PC , PLC حيث يمكن أن يتم ذلك من Control panel مباشرة ودون فتح برنامج Simatic manager حيث ستجد أيقونة خاصة بذلك في Control panel الخاصة بنظام التشغيل Windows تحت اسم Set PG/PC Interface حيث يتم الضغط على الأيقونة لفتح نافذة ضبط الاتصال واختيار وسيلة الاتصال المتوفرة فعليا لديك وبيانات الضبط الفعلية والآن فقد قطعت شوطا كبيرا في الاتصال قم بتوصيل وسيلة الاتصال حسب الضبط بين منفذ CPU ومنفذ جهازك والآن يمكنك عمل عملية من ثلاثة - يمكنك تحميل البرنامج الموجود على CPU عن طريق عمل Uploading - يمكنك نقل برنامج لديك إلى وحدة CPU عن طريق عمل Downloading - يمكنك عمل Monitoring لبيانات البرنامج داخل CPU بأكثر من طريقة _________________ أبـوروان | |
|
| |
PLCMan Admin
عدد الرسائل : 12366 العمر : 55 العمل/الترفيه : Maintenance manager تاريخ التسجيل : 02/03/2008
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الأربعاء 26 مايو 2010 - 10:30 | |
| | |
|
| |
Alewan جندي
عدد الرسائل : 9 العمر : 58 تاريخ التسجيل : 14/03/2010
| موضوع: رد: من منتديات شركة سيمنس (( سؤال وجواب )) الخميس 27 مايو 2010 - 8:01 | |
| الاخ العزيز نشكرلكم حسن اهتمامكم وسرعة الرد وهذا يدل على الاخلاق والكرم الكبير للمساعدة في توصيل المعلومات. مهندس حسن انا أستعمل كبيل الانترنيت للتوصيل مابين CPU , PC وكرت نوع ؤح5613 وكان الاتصال موجود مسبق ويعمل بصورة جيدة وعند فصلPCوالكوابل المتصلة معه للكشف على جهاز اخر وسلاك أخري بجانب PCوبعد اعادة التوصيل كمافي السابق لم نحصل على اتصل مابين CPU,PC وتضهر رسالة | |
|
| |